Free · No Login · Works On Site
728×90 Ad — Google AdSense Leaderboard
🔌
Ohm's Law
V = I × R

Fill in any two values — the third is calculated.

Result
💡
Power (Watts)
P = V × I

Fill in any two values — the third is calculated.

Result
📐
kVA ↔ kW Converter
kW = kVA × PF

Fill in any two to get the third.

Result
〰️
Single Phase Current
I = kW×1000 / (V×PF)
Full Load Current
Amps (A)
🔺
Three Phase Current
I = kW×1000 / (√3×V×PF)
Full Load Current
Amps (A) per phase
🔋
MCB / Fuse Size
In ≥ Ib
Minimum Breaker
🍳
Cooker Circuit Calculator
10A + 30% remainder + 5A

Calculates assessed demand using BS 7671 / IET OSG diversity for cookers, then recommends MCB and cable size, plus whether it needs a dedicated circuit.

Assessed Demand
Cooker Circuit — Key Rules
RequirementGuidanceSource
Dedicated circuitRequired when appliance exceeds 3kW (13A limit). Under 3kW can be supplied from a 13A socket on a ring main, though a fused spur is better practice for sustained loads above 2kWOSG / BS 7671 good practice
Control unitA cooker control unit (with or without socket) is required within 2m of the appliance, accessible and not above the cookerReg 553.1.6 / OSG
Typical protection30A or 32A MCB (Type B) is standard for most domestic cookersOSG Table A1
Typical cable6mm² T&E covers most single ovens/hobs up to ~32A; larger ranges may need 10mm²Verify via cable sizing calc
Induction hobsOften lower current draw than stated wattage due to diversity within the hob itself — check manufacturer dataManufacturer spec
Socket outletA single socket may be incorporated into the control unit — this adds 5A to the diversity calculationOSG Appendix A
🔌
Cable Size Calculator
It ≥ In / (Ca×Cg×Cc×Ci)

Calculates minimum cable CSA using BS 7671 Appendix 4 correction factors. Covers T&E (flat twin), SWA, and flex.

Recommended Minimum Cable Size
📉
Voltage Drop Calculator
Vd = (mV/A/m × I × L) / 1000
Voltage Drop
🔵
Conduit Fill Calculator
Fill ≤ 40% of conduit CSA

BS 7671 requires cables to fill no more than 40% of the conduit internal CSA to allow cables to be drawn in without damage.

Cable groups (number of each)

Fill Result
🔄
Ring Main Load Check
Ib ≤ 20A · Floor Area ≤ 100m²

A standard 32A ring final circuit in a domestic property. Check total load and floor area compliance.

Ring Circuit Assessment
🔌
Spur Assessment
Sockets on spur ≤ 1

Check if a spur off a ring circuit is within the limits of BS 7671 and GN3.

Spur Assessment
🌍
Prospective Fault Current
Isc = V / Zs
Prospective Fault Current
⚙️
Motor Starting Current
Istart ≈ FLC × Mult
Starting Current
💰
Running Cost Calculator
Cost = kWh × Rate
Annual Running Cost
📐
Max Demand Calculator
Pmax = Σ(P × DF)

Estimate the maximum demand for a domestic or small commercial installation.

Maximum Demand
🔋
Charge Time Estimator
t = kWh / charger kW

Estimate how long a vehicle will take to charge from a given state.

Estimated Charge Time
EV Circuit Current & Cable
I = P / (V × PF)

Calculate the design current and minimum cable size for a home EV charger circuit.

Design Current / Min MCB
📊
Max Demand Impact Check
Total demand after EV

Check if adding an EV charger overloads the existing supply — critical for DNSP / DNO assessment.

Supply Assessment
📉
EV Cable Voltage Drop
Vd = mV/A/m × I × L / 1000

Long garage / driveway runs often fail on voltage drop — check before you pull the cable.

Voltage Drop
EV Charger Quick Reference
Charger TypeCurrentSupplyTypical CableMCB
3-pin (granny)10ASingle phase2.5mm² T&E16A Type B
7kW home unit32ASingle phase6mm² T&E / SWA40A Type B
11kW unit16A/phaseThree phase2.5mm² 5-core20A Type B (×3)
22kW unit32A/phaseThree phase6mm² 5-core40A Type B (×3)
50kW DC rapidThree phaseManufacturer specPer design

All domestic EV charger installations in the UK require OZEV-approved equipment and must comply with BS 7671 Amendment 2 (Regulation 722). Smart charging capability is mandatory on new domestic installations.

☀️
Array Output Estimator
Output = kWp × irradiance × efficiency

Estimate annual and daily energy generation for a UK solar PV system.

Estimated Annual Generation
🔄
Inverter Sizing
Inverter kW ≈ 0.8–1.0 × Array kWp

Size the inverter to match the array — typically 80–100% of total panel kWp.

Recommended Inverter Size
🔌
Inverter AC Output Current
I = kW / (V × PF)

Calculate the AC current from the inverter to size the cable and protection device back to the consumer unit.

AC Output Current / Min MCB
📋
G98 / G99 Connection Check
G98 ≤ 16A/phase · G99 > 16A/phase

Determine whether the system requires a G98 notification or a full G99 application to the DNO.

Connection Route
💰
Annual Savings Estimator
Savings = self-use × rate + export × SEG rate

Estimate annual bill savings and export income — useful for customer quotes.

Estimated Annual Benefit
Solar PV Quick Reference
ItemDetailNotes
G98 notification≤3.68kW single phase (16A)Notify DNO within 28 days of commissioning
G99 application>3.68kW or >16A/phasePre-approval required before installation
MCS certificationRequired for SEG paymentsAlso required for planning exemptions
Typical UK yield900–1100 kWh/kWp/yrVaries by region, pitch and orientation
String fuse (DC)Per manufacturer specRequired if >2 strings in parallel
AC cable (inverter)Size per inverter output currentTreat as continuous load — apply 125%
RCD protectionType A minimum (Type B if no isolation transformer)Check inverter manufacturer requirements
IsolationAC isolator adjacent to inverterDC isolator required at array and inverter
Common Formulas
FormulaDescriptionVariables
V = I × ROhm's Law — VoltageV=Volts, I=Amps, R=Ohms
P = V × ISingle phase powerP=Watts
P = I² × RPower from current & resistance
I = P / (√3 × V × PF)3-phase full load current√3 ≈ 1.732
Vd = (mV/A/m × Ib × L) / 1000Voltage drop (BS 7671 method)L in metres
It ≥ In / (Ca×Cg×Cc×Ci)Cable tabulated current neededCorrection factors
Isc = Vp / ZsProspective fault currentZs = loop impedance
kW = kVA × PFReal vs apparent powerPF = power factor
E = P × t / 1000Energy (kWh)P=Watts, t=hours
cos φ = kW / kVAPower factor angleφ = phase angle
BS 7671 Max Zs Values — Common Devices
DeviceRatingMax Zs (Ω) — 0.4sMax Zs (Ω) — 5s
Type B MCB6A7.67
Type B MCB16A2.87
Type B MCB20A2.30
Type B MCB32A1.37
Type B MCB40A1.15
Type C MCB16A1.44
Type C MCB32A0.72
Type D MCB16A0.72
30mA RCDAny1667Ω max

BS 88 fuse Zs values are not shown here as they vary between fuse standards (BS 88-2, BS 88-3) and disconnection time — always check BS 7671 Table 41.4 or manufacturer data directly for fuse-protected circuits.

Standard Cable Current Ratings (70°C PVC, Clipped Direct)
CSA2-core (A)3-core (A)Max V-drop (mV/A/m)
1.0mm²14.513.544
1.5mm²18.517.529
2.5mm²252318
4.0mm²323011
6.0mm²43387.3
10mm²57524.4
16mm²75682.8
25mm²96871.8
35mm²1191071.3
50mm²1501340.95
70mm²1851680.65
95mm²2322100.49
Minimum Earth Conductor Sizes (BS 7671 Table 54.7)
Phase/Line ConductorMin CPC (same material)Min CPC (different material)
≤16mm²Same CSA as phaseEquivalent conductance
16mm² – 35mm²16mm²Equivalent conductance
>35mm²Half the phase CSAEquivalent conductance
728×90 Ad — Google AdSense Leaderboard